My quote(0)

RTU

Remote Unit for Signal Monitoring and Digitization

Modular remote unit for gathering and digitizing field signals, integrating devices with supervisory and monitoring systems.

Configure your quote

At a glance

What it is for

Gathering, digitizing and sending field signals from substations and industrial plants to the supervisory system.

What defines the choice

  • Modular: power supply, CPU, optional communication module and up to 8 I/O modules
  • Digital and analog inputs and outputs, PT100 and PNP/NPN
  • Up to 5 communication ports for SCADA systems
  • Options with IEC 61850, fiber optics, SFP Ethernet, Wi-Fi and NB-IoT
  • Free configuration software, MQTT connection and Bluetooth

When to choose this model

When there are many signals to integrate or a concentrator is needed for SCADA or Monitrafo, instead of connecting each device separately.

To configure your quote

List the signals to be connected (digital, analog and PT100 inputs and outputs) and the supervisory protocol. In the configurator, choose the power supply, the CPU with its communication ports and the module for each of the 8 slots.

Description

Electron do Brasil's RTU (Remote Terminal Unit) is a microprocessor-based device with high capacity for data acquisition, monitoring, indication, control and supervision. Its reliability and efficiency make it a robust, versatile, configurable solution with numerous application possibilities.

The RTU offers many implementation advantages. Its software is free to download and use, easy to learn and simple to configure. Module configuration is fully flexible, allowing the user to specify the product to best suit the application. It can be configured to provide up to 5 communication ports for SCADA systems. The device's programming logic is unlimited. Internet connectivity through an MQTT broker provides access to status and parameters via a web page or mobile app, with Bluetooth pairing.

The RTU is a modularly configurable device, meaning that the number of modules must be specified to meet the intended application. The standard Electron RTU configuration consists of:

1 Power Supply Module (RTU-PW).

1 CPU Module (RTU-CPU).

1 Communication Module (RTU-DCM) (optional).

And up to 8 modules for input/output signal processing (DI, DO, AI, AO, PT-100, NPN/PNP) and/or dedicated modules.

The RTU is a compact device made of extruded aluminum with an electrostatic coating that protects it against external chemical agents. The aluminum enclosure protects the circuit boards against external noise and disturbances and provides excellent heat dissipation, extending the life of electronic components. It mounts on a 35 mm DIN rail on the panel backplate.

Technical data

POWER SUPPLY MODULE (PW)

Power Supply Input
• Operating voltage range: 85 to 265 VDC/VAC
• Operating frequency range: 50 to 60 Hz
• Operating temperature range: -40 to 85°C
• Power consumption: 15 W (PW-00 and PW-01) / 30 W (PW-02)

Auxiliary Output
• Output voltage: 24 VDC – Regulated
• Maximum current drawn: 83 mA
• Maximum power supplied: 2 W
• Galvanic isolation: 2 kV / 60 Hz / 1 minute

Fault Relay
• Contact rating / (resistive load): 125 VAC / 15 A, 250 VAC / 10 A, 24 VDC / 15 A
• Maximum switching current: 6 amperes
• Minimum switching current: 500 mW/12 V/10 mA
• Maximum switching power: 1500 VA – 180 W
• Maximum switching voltage: 400 VAC / 125 VDC
• Mechanical life: 10^6 operations minimum, 300 cycles (operations/minute);
• NO operate time: 8 ms (max.)
• Release time: 4 ms (max.)
• Dielectric strength between coil and contacts: 4000 VAC (RMS)
• Dielectric strength between open contacts: 1000 VAC (RMS)
• Initial insulation resistance: 1000 MΩ (500 VDC)
• Vibration resistance: 10–55 Hz (double amplitude 1.1 mm/6 G)

PROCESSING MODULE (CPU)

• The remote unit's RTU-CPU module always includes a Micro-USB port for configuration via software.

• Starting with model 09, the remote unit's RTU-CPU module includes a USB-C port for configuration via software.

• Micro SD Card slot for recording and storing monitored data on a Class 10 Micro SD Card (10 mB/s). Variables can be selected for recording, and logging is based on time and variation in the measured quantity (optional).

• RS-485 communication ports (ANSI/TIA/EIA-485-A), allowing different Slave protocols to be configured on each output and one Master port to be configured with the Modbus-RTU protocol.

• Multimode optical fiber (ST) communication port, resistant to EMI / RFI and current fluctuations, ideal for data communications near transformers, heavy electrical equipment and other sources of electrical or radio interference.

• SIM Card slot (NBIoT) for access to IoT monitoring through Monitrafo.com. The card can be purchased directly from an NBIoT provider (vivo, claro, Tim), or contact us for plan pricing.

• Internal modem with a 3 dBi antenna for connection to any WIFI network and transmission of protocols (Modbus, DNP3 and IoT). • SFP (Small Form-factor Pluggable) communication interface with up to 3 SFP ports: 2 Ethernet ports in Bridge mode (ETH1 and ETH2) and 1 RS485 serial port. These ports require 100 Mb/s SFP transceivers with LC / SC and RJ45 connectors.

COMMUNICATION MODULES (DCM)

• WIFI (Modbus TCP and RTU / DNP3 / MQTT);

• Bluetooth for parameter configuration via mobile APP and virtual HMI;

• TCP/IP communication input (Modbus TCP and RTU / DNP3 / MQTT);

• RS-485 serial input (Slave or dedicated Master);

• SIM Card slot (NBIoT) for access to IoT monitoring;

INPUT MODULES (INPUT)

• AI – ISOLATED ANALOG INPUT – 8 isolated analog inputs, 0…24 VDC and 0…20 mA;

• DI – ISOLATED DIGITAL INPUT – 8 isolated digital inputs, 24…300 VDC/VAC;

• PNI – PNP and NPN INPUT – 8 active PNP/NPN inputs, 0…24 VDC/5 mA per channel;

• RTDI – RTD – PT100 INPUT – 8 resistive signal inputs for PT-100 sensor readings (-50…850°C);

OUTPUT MODULES (OUTPUTS)

• AO – ISOLATED ANALOG OUTPUT – 8 isolated analog outputs, 0…24 VDC and 0…20 mA;

• DO – DIGITAL RELAY OUTPUT – 8 SPDT (NO/NC) digital relay outputs rated at 6 A;

DEDICATED MODULES (INPUT / OUTPUT)

• RBM – AIR CELL AND BLADDER RELAY – 1 liquid sensor input (SLE) dedicated to detecting transformer air cell and/or bladder rupture, or leaks

• MTTP – TEMPERATURE MONITORING (ANSI 23, 26, 49/49I) – 4 inputs for resistive signal readings from RTD PT-100 sensors.
4 inputs with a 4…20 mA range from split-core CTs for current signal readings.

• DVR – VOLTAGE REGULATOR (ANSI 90) – 4 inputs for voltage readings from 0 to 280 VAC (3 phases and neutral).
3 inputs for 0–10 A AC split-core CTs for phase current readings.

• MNO – LEVEL MONITOR (ANSI 71/71C) – 1 resistive signal input (magnetic float), with a 0…400 ohm range for transformer conservator oil level readings.
1 resistive signal input (magnetic float), with a 0…400 ohm range for oil level readings
in the transformer's on-load tap changer tank.

• OLTC-01 – ON-LOAD TAP CHANGER MOTOR TRANSDUCER – 1 input for voltage readings up to 350 VAC (phase-to-phase) + 1 input with a 4…20 mA range from a split-core CT for AC current signal readings from 1 phase of the on-load tap changer motor.

• OLTC-02 – ON-LOAD TAP CHANGER MOTOR TRANSDUCER – 1 input for voltage readings up to 350 VDC (phase-to-phase) + 1 input with an internal shunt resistor for direct AC current signal readings.

TYPE TESTS PASSED

• Applied voltage (IEC 60255-5): 2 kV / 60 Hz / 1 min. (to ground);

• Impulse voltage (IEC 60255-5): 1.2/50 µs / 5 kV / 3 negative and 3 positive / 5-second interval;

• Electrostatic discharge (IEC 60255-22-2): Air discharge = 8 kV / Contact discharge = 6 kV;

• Radiated electromagnetic disturbance immunity (IEC61000-4-3): 80 to 1000 MHz / 10 V/m;

• Electrical fast transient immunity (IEC60255-22-4): Power supply/inputs/outputs = 4 kV / common mode 2 kV;

• Surge immunity (IEC60255-22-5): Phase/neutral 1 kV, 5 per polarity (±) – phase-to-ground/neutral-to-ground 2 kV, 5 per polarity (±);

• Conducted electromagnetic disturbance immunity (IEC61000-4-6): 0.15 to 80 MHz / 10 V/m;

• Climatic test (IEC60068-21-14): -40°C to +85°C / 72 hours;

• Vibration endurance (IEC60255-21-1): 3 axes / 10 to 150 Hz / 2 G / 160 min/axis;

• Vibration response (IEC60255-21-1): 3 axes / 0.075 mm at 10 to 58 Hz / 1 G from 58 to 150 Hz / 8 min/axis;

Applications