RIN
Liquid Level Indicating Relay with Photoelectric Sensor
Level indication relay with a photoelectric sensor for detecting the presence or absence of liquid in tanks and equipment.
Description
The Level Indicating Relay (RIN) was developed to “detect the absence of liquid (oil, water, etc.) in corrugated-tank (hermetically sealed) transformers and liquid tanks in general,” with the aim of “continuously monitoring integrity for leaks.” This device is essential for ensuring industrial equipment safety and proper operation by detecting the absence of liquids that could compromise operation.
The RIN monitors liquid level through a photoelectric sensor. This sensor continuously detects the presence of liquid (oil, water or any liquid), operating at temperatures up to 120°C. The detection mechanism is based on light refraction.
According to the manual: “This sensor operates through light refraction. When the polysulfone dome, made of a material from the high-performance thermoplastic family, detects the absence of liquid, the sensor instantly detects internal variations caused by this refraction and immediately activates the relay in the sensor's power and control module.”
The RIN module is microprocessor-based, fully isolated and protected against electrical surges and induction, using state-of-the-art electronic components (SMD) and built to “strict quality standards.” Its hardware is designed to “withstand harsh operating conditions.”
The RIN can be installed directly in:
- Transformers and industrial-size tanks in power substations.
- Offshore platforms.
- Chemical plants.
It meets the requirements for performance, support and reliability specified by IEC, DIN, IEEE and ABNT standards.
Technical data
MAIN FEATURES
• Universal 48 to 265 VDC/VAC power supply;
• Microprocessor-based relay module with high operating speed;
• Compact 22.5 x 100 x 113.5 mm ABS enclosure for 35 mm DIN rail;
• AISI-304 stainless steel sensor, dimensions: 14 × 70 / M16 x 70 mm;
• 1 6 A relay with NO/NC contact and programmable logic;
• 1 6 A relay with NC contact for instrument or sensor fault indication (watchdog);
• Connectors with the exclusive “Pluggleble System” (pluggable);
• RS485 digital output with Modbus RTU or DNP 3 L1 protocol;
• Auto Baud Rate, with automatic communication speed detection and selection from 2,400 to 57,600 bps;
• Front USB Type-C port for parameter configuration using UseEasy™ software;
• Easy INSTALLATION and application;
• 2-year warranty;
TYPE TESTS PASSED
• Applied voltage (IEC 60255-5): 2 kV / 60 Hz / 1 min. (to ground);
• Impulse voltage (IEC 60255-5): 1.2/50 µs / 5 kV / 3 negative and 3 positive / 5-second interval;
• Electrical transient immunity (IEC 60255-4) (IEC 60255-6): 2.5 kV / 1.1 MHz / 2 s, 400 surges/s – Cycles;